Installation of Intelligent Electromagnetic Flowmeter Sensor on Process Pipeline

May 17, 2022

electricmagenatic flow meter(1)



  1. The intelligent electromagnetic flow measuring pipe must be completely filled with medium at any time, and it cannot work normally when the pipe is not full or empty. When the medium is not full in the pipe, the method of raising the height of the water outlet pipe at the rear end of the flowmeter can be used to fill the medium with the medium, so as to avoid the dissatisfied pipe and the gas from adhering to the electrode.


2. There is a vacuum in the pipeline, which will damage the lining of the flowmeter, so special attention should be paid to it.

3. The positive direction of flow should be consistent with the positive direction indicated by the arrow on the flow meter.

4. The intelligent electromagnetic flowmeter can be installed on straight pipelines or horizontal or inclined pipelines, but the central connection line of the two electrodes is required to be in a horizontal state.

5. For liquid and solid two-phase fluids, it is best to use vertical installation, so that the measured medium flows from top to bottom, which can make the flowmeter lining wear evenly and prolong its service life.

6. Make sure the flowmeter has enough space near the pipe flange for installation and maintenance.

7. If the measurement pipeline vibrates, there should be fixed supports on both sides of the flowmeter.

8. If the measurement medium is a heavily polluted liquid, install the flowmeter body in the bypass pipeline, and the flow can be emptied and cleared without interrupting the process operation.

9. When installing the Teflon-lined flowmeter, the bolts connecting the flange should be tightened evenly, otherwise the Teflon-lined lining will be easily crushed, and it is best to use a torque wrench.