Pressure gauge fault handling
Trouble phenomenon:.
A petrochemical enterprise's heavy oil main pressure alarm interlock system, because the pressure of the boiler fuel oil's heavy oil main pipe drops and the standby pump cannot start automatically, the heavy oil pressure continues to drop until the boiler interlock action cuts off the heavy oil and stops, causing a malfunction.
Failure analysis:.
Under normal circumstances, when the pressure of the heavy oil main pipe drops to a certain value, the standby pump should automatically start to keep the heavy oil at a certain flow and pressure. Now that the standby pump has not started, the electric contact pressure gauge indicates that the standby pump has not received a pressure drop signal , That is to say, the pressure transmitter of this system does not feel the change of the pressure of the main pipe:.
Approach:.
Purge the pressure guiding tube with steam, clean the membrane cavity of the instrument with gasoline, and perform a static pressure test on the instrument before reusing the instrument. After passing the inspection, fill the pressure guiding tube with isolating fluid again.
The pressure indicator returns to zero.