You must not know the important role of electric contact pressure gauge. Of course, in the water pump control system, electric contact pressure gauge plays a vital part. Why do you say that? Xiao Bian takes you to find out.

The electric contact pressure gauge is similar to the ordinary pressure gauge. It is based on the fact that the bourdon tube in the measuring system is forced to produce corresponding elastic deformation displacement at the end of the bourdon tube under the pressure of the measured medium. With the help of the pull rod, it is transmitted through the gear transmission mechanism and amplified. The indicator on the fixed gear (together with the contact) will indicate the measured value on the dial. The difference is that the electric contact pressure gauge has auxiliary contacts inside, which are usually used together with corresponding electrical devices (such as relays and frequency converters). When it contacts with the contact (upper or lower limit) on the setting pointer, the circuit in the signal system can be disconnected or connected, and the purpose of automatic control and signal (alarm) transmission of various gas and liquid media of the measured (controlled) pressure can be realized through the instrument.
The electric contact pressure gauge is widely used in petroleum, chemical, metallurgy, power station, machinery and other industrial departments, or in the matching of electromechanical equipment to measure the pressure of various fluid media without explosion risk. Now it is also widely used in the water supply and drainage system, among which the jockey pump and jockey pump in the fire protection system use the electric contact pressure gauge to control the start and stop of the pump to maintain the pressure in the pipe network stable within the required range.
Generally, the electric contact pressure gauge is connected to the water outlet pipe at the rear of the pump through the buffer pipe, the pressure signal control line is connected, and the pump secondary control circuit is connected. In theory, the control system is in the automatic state. When the pressure in the pipe reaches the low pointer pressure, the pump control system gets the pump start signal and the pump starts; When the pressure in the pipe rises to the high pointer pressure, the pump control system receives the pump stop signal and the pump stops.
During the actual commissioning, it was found that the pipe network of the hotel system was large, and the power, head and flow of the pump used in the fire fighting were large. Even if the buffer pipe was added, the large fluctuation of the pressure in the pipe during the pump start and stop could not be avoided, which directly led to the large and frequent shaking of the pointer of the pressure gauge. The pump control system constantly received the pump start and stop signals, and the pump would start and stop frequently, which could not achieve a good stabilizing effect, It is also easy to damage the pressure gauge, which may affect the service life of the pump or even directly cause the pump failure.